Model | OTM-TD150-JPHW12 | OTM-TD150-JPHW24 | |
Certificates | FCC UL cUL | FCC UL cUL | |
Output | DC Voltage | 12V | 24V |
Rated Current | 12.5A | 6.25A | |
Rated Power | 150W | ||
Voltage Tolerance | ±0.5V | ||
Voltage Regulation | ±0.5% | ||
Load Regulation | ±2% | ±1% | |
±1% | |||
Input | Voltage Range | 110-277VAC | |
Frequency Range | 47-63Hz | ||
Power Factor(Typ.)@ full load | 0.98@120VAC 0.95@277VAC | 0.99@120VAC 0.94@277VAC | |
THD(Typ.)@ full load | <20% | ||
Efficiency(Typ.)@ full load | 85% | 85% | |
AC Current(Max.) | 1.8A@110VAC | ||
Inrush Current (Typ.) | 15A, 50%, 1.4ms | ||
Leakage current | <0.50mA | ||
Protection | Short Circuit | shut down o/p voltage, re-power on to recover after fault condition is removed | |
Over Loading | ≤120% constant current limiting, auto-recovery | ||
Over temperature | 100℃±10℃ shut down o/p voltage, automatically recover after cooling. | ||
Environment | Working TEMP. | -40~+60℃ (see below derating curve) | |
Working Humidity | 20~90% RH, non-condensing | ||
Storage TEMP. Humidity | -40~+80℃,10~95%RH | ||
TEMP .coefficient | ±0.03%/℃(0~50℃) | ||
Vibration | 10~500Hz, 5G 10min./1 cycle,period for 60min. each along X,Y,Z axes | ||
Safety& EMC | Safety standards | ETL | |
Withstand voltage | I/P-O/P:1.88KVAC | ||
Isolation resistance | I/P-O/P:100MΩ/500VDC/25℃/70%RH | ||
EMC EMISSION | FCC Part 15 B | ||
others | Net. Weight | 1.8Kg | |
Size | 260*103*46mm (L*W*H) | ||
packing | 10PCS/CTN | ||
385*335*200mm 、20PCS/CTN | |||
Notes | 1. All parameters if NOT specially mentioned are measured at 120VAC input, rated load and 25℃ of ambient temperature. | ||
2. To extend the driver's using life ,please reduce the loading at lower input voltage. |
Feature
1.Small size,High efficiency,High reliability,Long life,IP 67 rating
2.Working temperature -40~+60℃
3.Protection: Overload,short-circuit pratection,Over-temperature
4.Low standby power,min to 0.3W
5.low output ripple noises
6.5 years guarantee
Application places
※ Input wire 18AWG Black and White to be connected to AC L and N ,Green wire go ground,
※Output wire 14AWG Red to LED Positive side (+) , Black to LED Negative side (-).
■Dimming Operation
※The Pulse-Width Modulation (PWM) of output voltage can be adjusted through input terminal of the AC phase line(L) by connection a phase/triac dimmer.
※Usually matching with Forward phase , leading edge , Magnetic low voltage, triac dimmers, or Reverse phase, trailing edge ,Electric low voltage Dimmers.
※Please try to use dimmers with power at least 1.5 times as the output power of the driver.
Connecting Diagram